top of page

The BRKLOV0009 is the 16-amp member of the Lovato DC breaker family used in Tornatech GPD diesel fire pump controller panels, occupying the CB1–CB2 positions on the electrical drawing. These breakers protect the controller's DC battery circuits, opening automatically if current exceeds the 16 A rating.

A breaker that trips as soon as it is reset, will not latch, or feels loose in its mounting should be replaced rather than forced. If tripping is repeated, check the downstream circuit for shorts before installing the new breaker: de-energize the DC circuit, transfer the wiring, and confirm the breaker holds under normal load.

Fits Tornatech GPD diesel fire pump controllers in the CB1-CB2 positions; verify the 16 A rating against your controller's drawing before ordering. Veteran-owned Cybertronic Controls in Hammond, Louisiana stocks Tornatech breaker replacements — call 985-351-5681 for help reading your panel drawing.

BRKLOV0009 DC Circuit Breaker – Tornatech GPD Diesel Controller, 16 A (CB1-CB2)

SKU: BRKLOV0009
$25.00Price
Quantity
    bottom of page